A three phase transformer has a nameplate rating of 30 MVA, 230Y/69Y kV with a leakage -reactance of 10% and the transformer connection is wye-wye. Choosing a base of 30MVA and 230 kV on high voltage side, the transformer reactance referred to the high voltage side will be _________(in ohms).

Correct Answer: 176.33 Ω
Zb=kVb2/MVAb(3-ph) = 2302/30 = 1763.33 Ω X Ω = Xpu*Xb(HV) = 0.1*1763.33 = 176.33 Ω.